LIST controller

LIST controller

LISTcontroler single and loop back

 

Features

  • The LISTcontroller represents the central control and evaluation unit, utilising an ARM9™ embedded processor and two additional distributed processors to continually, quickly, and reliably monitor temperatures
  • Sensor cable and unit redundancy via Loop-Back or Rerouted Data Transmission (LISTEC LB-/ RDT-function)
  • Alarm triggering via differential and maximum temperature evaluation
  • Up to 254 programmable individual zones with alarm and fault status signalling to superordinate systems via up to 16 relay modules with 16 relay contacts each
  • High temperature resolution of 0.1 °C with a repeatability of ±0.1 K along the entire sensor cable length
  • Free from false alarms, caused by natural ambient temperature fluctuations, due to intelligent evaluation algorithms
  • Alarm and fault indications via LEDs and LC-Display plain text messages in several languages
  • Signalling of alarm and fault status to superordinate systems via galvanically isolated relay contacts and/or data-interfaces with open data-protocols
  • Highly durable via utilisation of maintenance-free components in a modular configuration, RoHS compliant
  • Very low energy consumption
  • Flexible communication
  • Verified and approved to FprEN 54-22:2012 by VdS Schadenverhütung, VdS no.: G 213072. Meets requirements of environmental classification III
  • Web-interface
  • 8 languages configurable (Dutch, English, French, German, Italian, Polish, Spanish, Swedish)
  • Individual password-protected access levels for operators, maintenance and service personnel, as well as for commissioning

Front panel displays

  • Operation: LED green
  • Measuring cycle: LED blue
  • Data transmission: LED orange
  • Fire alarm SEC A/ SEC B: LED each red
  • Fault SEC A/ SEC B: LED each orange
  • LC-Display: Plain text messages and menu navigation

Front panel Operation

  • 5 button membrane keyboard for menu navigation, data and function input

System specifications

  • Measuring resolution: 0,1 °C
  • Repeatability:  0,1 K
  • Sensor quantity: Min. 10 / max. 500 (320 approved by VdS Schadenverhütung according to FprEN 54-22:2012)
  • Sensor cable length: Up to 3.200 m
Connections and interfaces

  • SEC1 / SEC2: SEC A / SEC B sensor cable connection (SEC 2 only with Loop Back or RDT-systems)
  • CONTROL I/O: RS485 data-interface to optional relay modules, as well as in/outputs (external reset, general relays for pre-alarm, alarm, fault, frost-alarm)
  • Power supply: 24 V DC
  • COM 1: RS485 data-interface for LIST master/slave or RDT-communication in a LIST network
  • Com 2: RS232  Service-interface for LISTEC GmbH only
  • Com 3: RS232 data-interface for unit parameterisation (Service-interface up to 115200 kb/s)
  • LAN: Ethernet network-interface with 100Mb/s for LIST RDT-communication as well as commissioning and maintenance via standard browsers
  • USB-host: To retrieve maintenance files and optionally saved alarm temperature data, as well as to transfer unit configurations and perform software updates

Supported software protocols

  • MODBUS (RTU) via serial interface COM2
  • 3964R (Siemens) via serial interface COM2
  • UGM 2005/2020 (Bosch) via serial interface COM2
  • EDP (Esser data protocol) via serial interface COM2
  • UGM 2040 (Bosch) via LAN interface
  • MODBUS TCP via LAN interface
  • IEC 60870-5-104 via LAN interface

General data

  • Operating temperature: -5 °C … +70 °C, (-25 °C feasible with the exception of an illegible LC-Display)
  • Dimensions: 482,6 x 43,6 x 315,5 mm (w x h x d), resembling a 19” – 1 U case, 400 mm depth to be considered with connection cables attached
  • Case material: Aluminium
  • Weight: 2,6 kg
  • Power supply: 9,5 V … 36 V DC
  • Current draw: Typ. 175 mA (Normal) / 212 mA (Alarm), at 24 V DC
  • Power consumption: Max. 5 W
  • Relay output: 1 Relay each for alarm, pre-alarm and frost-alarm 1 Relay for fault (= active without power)
  • Switching Voltage: 48 V DC / 32 V AC max.
  • Switching current: 250 mA max. (resistive load)
  • Input: 1 x external reset (5 V … 36 V DC)

Ordering information

  • LIST CONTROLLER SEC (Unit with one sensor cable connection)
  • LIST CONTROLLER LB (Unit with two sensor cable connections for Loop-Back or RDT mode)
  • RDT function for LIST CONTROLLER LB
  • I/P Interface and Protocol for LIST controller (via RS232 with MODBUS (RTU), via Ethernet with MODBUS TCP, one license per system)
  • FCP Interface and Protocol for LISTcontroller (via RS232 or TCP with protocol UGM (Bosch) or via RS232 with protocol EDP (ESSER), one license per system)
  • LISTcontroller I/P IEC 60870-5-104 (via Ethernet with protocol IEC 60870-5-104, one license per system)

Scope of delivery

  • LISTcontroller
  • Pre-assembled 3 m connection cable lengths for sensor cable, Control I/O, COM1 and power supply
  • List memory USB flash drive

Accessories

Posted in SEC 20 | Comments Off on Accessories

Cabinets

Posted in SEC 20 | Comments Off on Cabinets

Connection Cable

Posted in SEC 20 | Comments Off on Connection Cable

Connection Box

Posted in SEC 20 | Comments Off on Connection Box

Connection Module

Posted in SEC 20 | Comments Off on Connection Module

Data Management Unit

Posted in SEC 20 | Comments Off on Data Management Unit

Ethernet-Switch

Posted in SEC 20 | Comments Off on Ethernet-Switch

External Sensors

Posted in SEC 20 | Comments Off on External Sensors

LIST cable tester

Posted in SEC 20 | Comments Off on LIST cable tester

LIST controller

Posted in SEC 20 | Comments Off on LIST controller

Power Supply

Posted in SEC 20 | Comments Off on Power Supply

Relay Module

Posted in SEC 20 | Comments Off on Relay Module

SEC 20 Simulator

Posted in SEC 20 | Comments Off on SEC 20 Simulator

Sensor Cable

Posted in SEC 20 | Comments Off on Sensor Cable

Software

Posted in SEC 20 | Comments Off on Software

LIST controller

Power Supply

Power Supply PS 240x

Features

  • Optional stand-by batteries extend operation as an uninterrupted 24 V DC supply in accordance with EN 54-4:2006
  • Short-circuit proof and current limited integral switch-mode power supply
  • Constant monitoring of stand-by battery charge and internal resistance in accordance with EN 54-4:2006
  • Maximised stand-by battery life time due to deep discharge protection and temperature compensated charging
  • Quick and easy test function to perform self-test and determine stand-by battery internal resistance
  • Earth fault monitoring configurable
  • Front-panel status display via seven LED’s
  • Acoustic fault signal
  • Powder coated sheet steel housing or 19“ front-panel
  • VdS approved

Specifications PS240

  • Mains voltage: 230 V AC +10/-20%
  • Mains frequency: 47 … 63 Hz
  • Output voltage: Typ. 27,6 V DC at 20 °C
  • Output current: Max. 2,3 A
  • Operating temperature: -5 °C … +50 °C
  • Relative humidity: Max. 95% at 40 °C (No condensation)
  • Dimensions: 230,0 x 150,0 x 54,0 mm (w x h x d, power supply module only) 478,0 x 266,0 x 63,0 mm (w x h x d, mounted on 19“ front-panel, w = 19“, h = 6U)
  • Weight: 0,5 kg power supply module only / 2,0 kg mounted on 19“ front-panel
  • Front-panel colour: RAL 9002, grey-white
  • Battery charging capacity: Up to 60 Ah, chargeable to 80% within 24 hours without load

Specifications PS2402-W

  • Mains voltage: 230 V AC +10/-20%
  • Mains frequency: 47 … 63 Hz
  • Output voltage: Typ. 27,6 V DC at 20 °C
  • Output current: Max. 2,3 A
  • Operating temperature: -5 °C … +50 °C
  • Relative humidity: Max. 95% at 40 °C (No condensation)
  • Ingress protection: IP 30
  • Dimensions: 442,0 x 462,0 x 206,0 mm (w x h x d)
  • Weight: 6,7 kg (Including power supply module, but without additional components)
  • Housing colour: RAL 9002, grey-white
  • Battery installation: Max. two 12 V / 45 Ah within housing
  • Battery charging capacity: Up to 60 Ah, chargeable to 80% within 24 hours without load

Specifications PS2408

  • Mains voltage: 230 V AC +10/-20%
  • Mains frequency: 47 … 63 Hz
  • Output voltage: Typ. 27,6 V DC at 20 °C
  • Output current: Max. 8.4 A
  • Operating temperature: -5 °C … +50 °C
  • Relative humidity: Max. 95% at 40 °C (No condensation)
  • Dimensions: 292,0 x 220,0 x 72,0 mm (w x h x d, power supply module only) 478,0 x 266,0 x 83,0 mm (w x h x d, mounted on 19“ front-panel, w = 19“, h = 6U)
  • Weight: 2,2 kg power supply module only / 3,8 kg mounted on 19“ front-panel
  • Front-panel colour: RAL 9002, grey-white
  • Battery charging capacity: Up to 220 Ah, chargeable to 80% within 24 hours without load

Specifications PS2408-W

  • Mains voltage: 230 V AC +10/-20%
  • Mains frequency: 47 … 63 Hz
  • Output voltage: Typ. 27,6 V DC at 20 °C
  • Output current: Max. 8,4 A
  • Operating temperature: -5 °C … +50 °C
  • Relative humidity: Max. 95% at 40 °C (No condensation)
  • Ingress protection: IP 30
  • Dimensions: 442,0 x 462,0 x 206,0 mm (w x h x d)
  • Weight: 8,4 kg (Including power supply module, but without additional components)
  • Housing colour: RAL 9002, grey-white
  • Battery installation: Max. two 12 V / 45 Ah within housing
  • Battery charging capacity: Up to 220 Ah, chargeable to 80% within 24 hours without load

Ordering information

  • PS 4202 (Power supply mounted on 19“ front-panel)
  • PS 2402-W (Power supply mounted in housing)
  • PS 2408 (Power supply mounted on 19“ front-panel)
  • PS 2408 -W (Power supply mounted in housing)

Scope of delivery

  • PS 4202 with mounting accessories and documentation
  • PS 2402-W with mounting accessories and documentation
  • PS 2408 with mounting accessories and documentation
  • PS 2408-W with mounting accessories and documentation

Accessories

Posted in SEC 20 | Comments Off on Accessories

Cabinets

Posted in SEC 20 | Comments Off on Cabinets

Connection Cable

Posted in SEC 20 | Comments Off on Connection Cable

Connection Box

Posted in SEC 20 | Comments Off on Connection Box

Connection Module

Posted in SEC 20 | Comments Off on Connection Module

Data Management Unit

Posted in SEC 20 | Comments Off on Data Management Unit

Ethernet-Switch

Posted in SEC 20 | Comments Off on Ethernet-Switch

External Sensors

Posted in SEC 20 | Comments Off on External Sensors

LIST cable tester

Posted in SEC 20 | Comments Off on LIST cable tester

LIST controller

Posted in SEC 20 | Comments Off on LIST controller

Power Supply

Posted in SEC 20 | Comments Off on Power Supply

Relay Module

Posted in SEC 20 | Comments Off on Relay Module

SEC 20 Simulator

Posted in SEC 20 | Comments Off on SEC 20 Simulator

Sensor Cable

Posted in SEC 20 | Comments Off on Sensor Cable

Software

Posted in SEC 20 | Comments Off on Software

BS 7835 XLPE  LSZH 19/33 (36)kV

BS 7835 XLPE LSZH 19/33 (36)kV

Cable construction

ConductorClass 2 stranded copper conductor according to BS EN 60228
Conductor screenSemi-conductive XLPE (Cross-Linked Polyethylene)
InsulationXLPE (Cross-Linked Polyethylene)
Insulation screenSemi-conductive XLPE (Cross-Linked Polyethylene)
Metallic screenIndividual or overall copper tape screen according to BS 6622
FillerPET (Polyethylene Terephthalate) fibres
SeparatorBinding tape
BeddingLSZH (Low Smoke Zero Halogen)
ArmourSingle core: AWA (Aluminium Wire Armoured)
Multi-core: SWA (Steel Wire Armoured)
SheathLSZH (Low Smoke Zero Halogen)

Dimensions

No. of CoresNominal Cross Sectional Area mm²Nominal DiameterNominal Weight kg/km
Under ArmourOver ArmourOverall
17032.636.6412300
19534.338.342.92650
112035.939.944.53000
115037.542.547.33500
118539.344.349.34000
124041.746.751.74650
130044.249.254.45450
140047.352.357.76350
150050.555.561.17600
163054.259.2659150
180060.565.571.611100
11000657076.513400
35065.171.478.29150
37068.875.182.110300
39572.678.986.111600
312076.382.69012800
315079.385.693.214050
318583.489.797.515650
324088.895.1103.318200
330093.9100.2108.821100
3400100.8107.1116.124200
Class 2 Stranded Conductors for Single Core and Multi-Core Cables
Nominal Cross
Sectional Area mm²
Minimum No. Of Wires In ConductorMaximum Resistance
of Conductor At 20ºC
CircularCircular CompactedShapedAnnealed Copper Conductor
CuAlCuAlCuAlPlain Wires ohms/km
50191966660.387
701919121212120.268
951919151515150.193
1203737181518150.153
1503737181518150.124
1853737303030300.0991
2403737343034300.0754
3006161343034300.0601
4006161535353530.047
6309191535353530.0283
80091915353--0.0221
100091915353--0.0176
Current Carrying Capacity
Nominal Cross
Sectional Area mm²
Continuous Current Rating
In Ground
Amps
In Ducts
Amps
In Air
Amps
TrefoilFlatTrefoilFlatTrefoilFlat
70270280260270310370
95320335305325375460
120360380340370430530
150410430375410490600
185455485410460550690
240 520560470540650820
300580640500610740940
4006507305306908401100
5007108305707809301280
63076094062089010401480
800 810106066099011401690
1000860117069019012301900
50210210180180220220
70250250215215270270
95300300255255330330
120340340290290380380
150380380330330430430
185430430370370490490
240500500430430570570
300540540470470650650
400600600530530740740
De-rating Factors
Air Temperature °C
25303540455055
DE-RATING FACTOR1.000.960.920.880.830.780.73
Ground Temperature10152025303540
DE-RATING FACTOR1.031.000.970.930.890.860.82
Ground Thermal Resistivity0.91.01.21.5 2.02.53.0
DE-RATING FACTOR1.06 1.041.000.920.82 0.740.68
Depth Of Laying0.801.001.25 1.501.752.02.50
DE-RATING FACTOR1.000.970.950.940.930.910.90

 

power-accessories01

Our power cables have many accessories.

For more information, don’t hesitate to call us on 0121 508 6890 or get in touch via our Contact Page.

NA2XS(FL)2Y Aluminium Conductor XLPE PE- 18/30 (36)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on NA2XS(FL)2Y Aluminium Conductor XLPE PE- 18/30 (36)kV Cable

NA2XS(FL)2Y Aluminium Conductor XLPE PE-12/20 (24)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on NA2XS(FL)2Y Aluminium Conductor XLPE PE-12/20 (24)kV Cable

NA2XS(FL)2Y Aluminium conductor XLPE PE-6/10 (12)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on NA2XS(FL)2Y Aluminium conductor XLPE PE-6/10 (12)kV Cable

NA2XS(F)2Y Aluminium Conductor XLPE PE – 18/30k (36)V Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on NA2XS(F)2Y Aluminium Conductor XLPE PE – 18/30k (36)V Cable

NA2XS(F)2Y Aluminium Conductor XLPE PE – 12/20 (24)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on NA2XS(F)2Y Aluminium Conductor XLPE PE – 12/20 (24)kV Cable

NA2XS(F)2Y Aluminium Conductor XLPE PE – 6/10 (12)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on NA2XS(F)2Y Aluminium Conductor XLPE PE – 6/10 (12)kV Cable

NA2XS2Y Aluminium Conductor XLPE PE – 18/30k (36)V Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on NA2XS2Y Aluminium Conductor XLPE PE – 18/30k (36)V Cable

NA2XS2Y Aluminium Conductor XLPE PE – 12/20 (24)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on NA2XS2Y Aluminium Conductor XLPE PE – 12/20 (24)kV Cable

NA2XS2Y Aluminium Conductor XLPE PE – 6/10 (12)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on NA2XS2Y Aluminium Conductor XLPE PE – 6/10 (12)kV Cable

N2XS(FL)2Y – 12/20 (24)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on N2XS(FL)2Y – 12/20 (24)kV Cable

N2XS(FL)2Y – 6/10 (12)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on N2XS(FL)2Y – 6/10 (12)kV Cable

N2XS(F)2Y – 18/30 (36)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on N2XS(F)2Y – 18/30 (36)kV Cable

N2XS(F)2Y XLPE PE – 12/20 (24)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on N2XS(F)2Y XLPE PE – 12/20 (24)kV Cable

N2XS(F)2Y XLPE PE – 6/10 (12)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on N2XS(F)2Y XLPE PE – 6/10 (12)kV Cable

N2XS2Y XLPE PE – 18/30 (36)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on N2XS2Y XLPE PE – 18/30 (36)kV Cable

N2XS2Y XLPE PE – 12/20 (24)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on N2XS2Y XLPE PE – 12/20 (24)kV Cable

N2XS2Y XLPE PE – 6/10 (12)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on N2XS2Y XLPE PE – 6/10 (12)kV Cable

NA2XSY Aluminium Conductor XLPE PVC – 18/30 (36)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on NA2XSY Aluminium Conductor XLPE PVC – 18/30 (36)kV Cable

NA2XSY Aluminium Conductor XLPE PVC – 12/20 (24)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on NA2XSY Aluminium Conductor XLPE PVC – 12/20 (24)kV Cable

NA2XSY Aluminium Conductor XLPE PVC – 6/10 (12)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on NA2XSY Aluminium Conductor XLPE PVC – 6/10 (12)kV Cable

N2XSEY XLPE PVC – 6/10 (12)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on N2XSEY XLPE PVC – 6/10 (12)kV Cable

N2XSY XLPE PVC – 18/30 (36)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on N2XSY XLPE PVC – 18/30 (36)kV Cable

N2XSY XLPE PVC – 12/20 (24)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on N2XSY XLPE PVC – 12/20 (24)kV Cable

N2XSY XLPE PVC – 6/10 (12)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on N2XSY XLPE PVC – 6/10 (12)kV Cable

BS 6622 XLPE MDPE 6.35/11 (12)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on BS 6622 XLPE MDPE 6.35/11 (12)kV Cable

BS 6622 XLPE PVC 6.35/11 (12)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on BS 6622 XLPE PVC 6.35/11 (12)kV Cable

BS 7835 XLPE LSZH 6.35/11 (12)kV

BS 7835 XLPE LSZH 6.35/11 (12)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on BS 7835 XLPE LSZH 6.35/11 (12)kV

BS 7835 XLPE LSZH 19/33 (36)kV

 

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on BS 7835 XLPE LSZH 19/33 (36)kV

BS 6622 XLPE PVC 19/33 (36)kV

BS 6622 XLPE PVC 19/33 (36)kV Cable

Posted in Power Generation, Power Medium Voltage Cable | Comments Off on BS 6622 XLPE PVC 19/33 (36)kV

LIST controller

Relay Module

Relay Module RELMOD

Features

  • Relay extension for LISTcontrollers to signal alarm and fault statuses to superordinate systems
  • Up to 16 relay modules are addressable per LISTcontroller
  • Contact multiplication programmable
  • Activation of a single relay by multiple zones programmable
  • Highly durable via utilisation of maintenance-free components in a modular configuration, RoSH compliant
  • Very low energy consumption
  • Coding Switch for module address (1 … 16)
  • Inputs to remotely activate revision-mode and to initiate alarm simulations
  • Inputs for external alarm- and fault-handling signals
  • Input to trigger timer-controlled deactivation of differential temperature monitoring
Displays at Relay Module

  • Operation: LED orange
  • Data transmission: LED blue
  • Fault: LED orange

Connections and Interfaces

  • 24 V DC: Power supply
  • COM (In / Out): RS485 interfaces to LISTcontroller or further relay module
  • Optocoupler inputs: For external signal input
  • Relay outputs: For signalling of alarms, pre-alarmes, frost-alarms and faults to superordinate systems
General data

  • Operating temperature: 0 °C … +70 °C
  • Dimensions: 167x 113,3 x 66,2 mm (w x h x d), snap on to 35 mm DIN-Rail
  • Case material: Aluminium with transparent acrylic glass shield above main components
  • Weight: 0,61 kg
  • Power supply: 10 V … 36 V DC
  • Current draw: 56 mA (normal operation) / 105 mA (alarm), at 24 V DC
  • Power consumption: Max. 2,5 W
  • Relay outputs: 16 x toggle contacts for alarm, pre-alarm, frost-alarm and fault (loop resistors may be inserted for closed-circuit monitoring)
  • Switching voltage: 48 V DC / 32 V AC max
  • Switching current: 250 mA max. (resistive load)
  • Optocoupler inputs: 8 x electrically isolated, 5…28 V DC signals

Ordering information

  • Relay Module RELMOD

Scope of delivery

  • Relay Module for DIN-Rail installation

Accessories

Posted in SEC 20 | Comments Off on Accessories

Cabinets

Posted in SEC 20 | Comments Off on Cabinets

Connection Cable

Posted in SEC 20 | Comments Off on Connection Cable

Connection Box

Posted in SEC 20 | Comments Off on Connection Box

Connection Module

Posted in SEC 20 | Comments Off on Connection Module

Data Management Unit

Posted in SEC 20 | Comments Off on Data Management Unit

Ethernet-Switch

Posted in SEC 20 | Comments Off on Ethernet-Switch

External Sensors

Posted in SEC 20 | Comments Off on External Sensors

LIST cable tester

Posted in SEC 20 | Comments Off on LIST cable tester

LIST controller

Posted in SEC 20 | Comments Off on LIST controller

Power Supply

Posted in SEC 20 | Comments Off on Power Supply

Relay Module

Posted in SEC 20 | Comments Off on Relay Module

SEC 20 Simulator

Posted in SEC 20 | Comments Off on SEC 20 Simulator

Sensor Cable

Posted in SEC 20 | Comments Off on Sensor Cable

Software

Posted in SEC 20 | Comments Off on Software

LIST controller

SEC 20 Simulator

SEC 20 Simulator CSM 200

 

Features

  • Designed to simulate sensor cable SEC 20 in test set-ups
  • Simulation of up to 200 sensors
  • Two temperature sensors available on-board for manual heat-up or cool-down tests
  • Additional facilities to connect up to two sensor cables SEC 20 and an external temperature sensor ESA
  • Four push buttons, configurable with alternative temperature values, to simulate maximum temperature, differential temperature and differential temperature pre-alarms, as well as sensor loss.
  • Test set-ups with redundant LIST systems can be realised by using two or more CSM 200
  • 35 mm DIN-rail mount

Specifications

  • Operating temperature: 0 °C … +40 °C
  • Dimensions: 102,5 x 82,0 x 42,0 mm (w x h x d, for 35 mm DIN-rail mount)
  • Weight: 0,13 kg
  • Number of sensors: Up to 200 (contiguous address range)
  • Sensor address range: 0 … 999
  • Power supply: During operation by LISTcontroller via connection cable VK SEC during set-up by PC via USB- cable

Ordering information

  • SEC 20 Simulator CSM 200

Scope of delivery

  • CSM 200 (pre-programmed with LISTEC default set-up)
  • USB-cable, type A-B
  • LISTmemory USB flash drive, including CSM 200 driver, software and documentation

Application software

  • System prerequisites: PC with Windows XP Service Pack 3 and JavaRuntimeEnviroment from Version 6.35 onwards

Accessories

Posted in SEC 20 | Comments Off on Accessories

Cabinets

Posted in SEC 20 | Comments Off on Cabinets

Connection Cable

Posted in SEC 20 | Comments Off on Connection Cable

Connection Box

Posted in SEC 20 | Comments Off on Connection Box

Connection Module

Posted in SEC 20 | Comments Off on Connection Module

Data Management Unit

Posted in SEC 20 | Comments Off on Data Management Unit

Ethernet-Switch

Posted in SEC 20 | Comments Off on Ethernet-Switch

External Sensors

Posted in SEC 20 | Comments Off on External Sensors

LIST cable tester

Posted in SEC 20 | Comments Off on LIST cable tester

LIST controller

Posted in SEC 20 | Comments Off on LIST controller

Power Supply

Posted in SEC 20 | Comments Off on Power Supply

Relay Module

Posted in SEC 20 | Comments Off on Relay Module

SEC 20 Simulator

Posted in SEC 20 | Comments Off on SEC 20 Simulator

Sensor Cable

Posted in SEC 20 | Comments Off on Sensor Cable

Software

Posted in SEC 20 | Comments Off on Software

LIST controller

Sensor Cable

Sensor specifications

  • Measurement range: -40 °C … +200 °C
  • Measurement resolution: 0,1 °C
  • Repeatability: 0,1 K
  • Supply voltage: 5 V DC via LIST controller

Ordering information

  • Sensor Cable SEC 20/01 (1 m sensor spacing)
  • Sensor Cable SEC 20/02 (2 m sensor spacing)
  • Sensor Cable SEC 20/03 (3 m sensor spacing)
  • Sensor Cable SEC 20/04 (4 m sensor spacing)
  • Sensor Cable SEC 20/05 (5 m sensor spacing)
  • Sensor Cable SEC 20/06 (6 m sensor spacing)
  • Sensor Cable SEC 20/08 (8 m sensor spacing)
  • Sensor Cable SEC 20/xx (Customer specified sensor spacing, limited to not less than 0,5 m)
  • ATEX marking for sensor cable SEC 20 (to be ordered for every separate sensor cable section)

Sensor Cable SEC 20-Ex

 

Features

  • ATEX marking for use in zones 2 and 22
  • Complete encapsulation to protect sensors from environmental influences
  • Sensor spacing selectable to comply to project demand
  • Pinpoint sensor location via individual addresses
  • Maintenance free cable
  • Aramid fibres serve as strain relief and as reinforcement in case of fire
  • Easy mounting by use of diverse fasteners
  • Branching of cable routes via connection boxes
  • To be used with sensor control unit LIST controller
  • May be combined with LIST external sensors ESA
  • Up to 3.200 m combined cable length, respectively up to 320 sensors per LIST controller

General data

  • Type of protection zone 2: Ex II 3G Ex nA IIC T4 Gc
  • Operating temp. zone 2: -20 °C … +80 °C, from 70 °C protected from mechanical impact energy (EN 60079-0 / 26.4.2)
  • Type of protection zone 22: Ex II 3D Ex tc IIIC T125 °C Dc
  • Operating temp. zone 22: -20 °C … +70 °C
  • Cable diameter: Typ. 18 mm
  • Flat conductor resistance: Typ. 85 Ω / km (single conductor)
  • Sheath material: HM4 mixture, halogen-free and flame retardant, according to EN 50267-2-1:1999-04,EN50267-2-2:1999-04, EN 60332-1-2:2005-06, EN 60332-2-2:2005-06, EN 61034-2:2006-03, IEC 60754-1, IEC 60754-2
  • Weight: Typ. 0,45 kg / m
  • Sheath colour: Grey or black
  • Marking: Consecutive number printed at each sensor location, followed by cable identifier
  • Deliverable cable length: Up to 2.000 m, prefabricated cable sections on request
  • Mounting temperature: ≥ +10 °C
  • Bending radius: ≥ 30 cm
  • Verified and approved to: FprEN 54-22:2012 by VdS Schadenverhutung, VdS no.: G 213072 Meets requirements of environmental classification III
Scope of delivery

  • Ordered sensor cable length may be shipped as a cable ring in a carton, on a one way drum, or on loaner KTG-drum and pallet
  • ATEX markings for every separate sensor cable section

Cable construction

  • Four-core flexible flat cable with temperature sensors
  • Filler material with strain relief
  • Aluminium foil shield
  • Sheath with imprints at each sensor location

Cable Imprint sec 20 imprint

  • Imprint 1: The sensor marking is used in cable lists, delivery notes etc.
  • Imprint 2: Static marking only

Accessories

Posted in SEC 20 | Comments Off on Accessories

Cabinets

Posted in SEC 20 | Comments Off on Cabinets

Connection Cable

Posted in SEC 20 | Comments Off on Connection Cable

Connection Box

Posted in SEC 20 | Comments Off on Connection Box

Connection Module

Posted in SEC 20 | Comments Off on Connection Module

Data Management Unit

Posted in SEC 20 | Comments Off on Data Management Unit

Ethernet-Switch

Posted in SEC 20 | Comments Off on Ethernet-Switch

External Sensors

Posted in SEC 20 | Comments Off on External Sensors

LIST cable tester

Posted in SEC 20 | Comments Off on LIST cable tester

LIST controller

Posted in SEC 20 | Comments Off on LIST controller

Power Supply

Posted in SEC 20 | Comments Off on Power Supply

Relay Module

Posted in SEC 20 | Comments Off on Relay Module

SEC 20 Simulator

Posted in SEC 20 | Comments Off on SEC 20 Simulator

Sensor Cable

Posted in SEC 20 | Comments Off on Sensor Cable

Software

Posted in SEC 20 | Comments Off on Software