Cable Construction
Conductor1.0mm² to 1.5mm²: Class 5 tinned copper conductor according to BS EN 60228 (previously BS 6360)
2.5mm² and above: Class 2 tinned copper conductor according to BS EN 60228 (previously BS 6360)
InsulationHalogen free elastomer EPR Type GP4 according to BS 7655
Inner SheathHOFR (Heat and Oil Resistant and Flame Retardant), halogen-free elastomer Type SW4 according to BS 7655
ArmourGalvanized steel wire braid*
Outer SheathHOFR (Heat and Oil Resistant and Flame Retardant), halogen-free elastomer Type SW4 according to BS 7655
BeddingSuitable tape between the braid and outer sheath
Note* Tinned copper wire braid version available on request

Dimensions

No. of CoresConductor ClassNominal Cross Sectional Area mm²Nominal Thickness of Insulation mmNominal Thickness of Inner Sheath mmNominal Diameter of Steel Wires in Braid mmNominal Thickness of Outer Sheath mmNominal Overall Diameter mmNominal Weight kg/km
2510.810.31.211.6200
251.50.81.10.31.212.4241
222.50.81.10.31.213.4283
22411.20.31.315.6387
22611.20.31.416.9476
221011.30.31.419.2627
221611.40.31.522853
22251.21.50.31.726.11212
22351.21.60.31.828.81532
22501.41.70.452332038
22701.41.90.452.137.12680
22951.62.10.452.342.23593
221201.62.20.452.546.24291
221501.82.30.452.650.55120
2218522.50.452.855.76404
222402.22.80.453.162.88210
223002.430.453.369.110016
3510.81.10.31.212.2237
351.50.81.10.31.212.9263
322.50.81.10.31.314.1323
32411.20.31.316.3439
32611.20.31.417.7547
321011.30.31.520.4743
321611.40.31.623.31029
32251.21.60.31.827.81515
32351.21.70.451.931.42032
32501.41.80.452352547
32701.420.452.239.63340
32951.62.20.452.445.54514
321201.62.30.452.649.35408
321501.82.50.452.854.36587
3218522.70.45359.98197
322402.22.90.453.26710475
323002.43.20.453.574.112878
4510.81.10.31.212.9262
451.50.81.10.31.313.9301
422.50.81.10.31.315.1384
42411.20.31.417.7532
42611.30.31.519.4673
421011.40.31.622.3917
421611.50.31.725.61287
42251.21.70.451.931.31999
42351.21.80.45234.22525
42501.41.90.452.238.73159
42701.42.10.452.443.74226
42951.62.30.452.650.25718
421201.62.50.452.854.66876
421501.82.70.45360.18357
4218522.90.453.266.310406
422402.23.20.453.574.613363
423002.43.50.453.882.416433
551.50.81.10.31.314.8351
522.50.81.20.31.316.3441
751.50.81.20.31.316.8452
722.50.81.20.31.418.6577
1251.50.81.30.31.520.1621
1222.50.81.40.31.622.6836
1951.50.81.40.31.624.1888
1922.50.81.50.31.727.11202
2751.50.81.60.31.827.51162
2722.50.81.70.451.931.41714
37*51.50.81.70.451.932.11608

* Based on Standard

Class 2 Stranded Conductors for Single Core and Multi-Core Cables

Nominal Cross
Sectional Area mm²
Minimum No. Of Wires In ConductorMaximum Resistance
of Conductor At 20ºC
CircularAnnealed Copper Conductor
CuMetal-Coated Wires ohms/km
2.577.56
474.7
673.11
1071.84
1671.16
2570.734
3570.529
50190.391
70190.27
95190.195
120370.154
150370.126
185370.1
240370.0762
300610.0607

Class 5 Flexible Conductors for Single Core and Multi-Core Cables
Nominal Cross Sectional Area mm²Maximum Diameter of Wires in Conductor mmMaximum Resistance of Conductor at 20°C
Plain Wires ohms/kmMetal-Coated Wires ohms/km
10.2119.520
1.50.2613.313.7

Current Carrying Capacity
Nominal Cross
Sectional Area mm²
Single Core
Amps
2 Core
Amps
3 and 4 Core
Amps
5 Core
Amps
7 Core
Amps
10 Core
Amps
12 Core
Amps
16 Core
Amps
19 Core
Amps
20 Core
Amps
24 Core
Amps
27 Core
Amps
30 Core
Amps
37 Core
Amps
118151310.59887776665
1.52320161210998776.56.566
2.5302621161513121110109.5998
4403428-----------
6524436-----------
10726150-----------
16968267-----------
2512710889-----------
35157133110-----------
50196167137-----------
70242206169-----------
95293249205-----------
120339288237-----------
150389331272-----------
185444377311-----------
240522444365-----------
300601511421-----------

Ambient Air Temperature of 45°C

De-Rating Factors

Ambient Temperature °C
35404550556065707580
DE-RATING FACTOR1.11.0510.940.880.820.740.670.580.47

Where more than six bunched cables on cable trays, in cable conduits, pipes or trunking are to expected to operate simultaneously full rated capacity, a correction of 0.85 should be applied