  • The area being protected was 70m x 35m with an apex roof.
  • The sensor cable clamps were secured on the roof purlins at 750mm intervals using self-drill tex screws.
  • 400m SEC15 sensor cable was then installed within 4 hours once the clamps were installed.
  • 2 x connections boxes located within 25cm of the SCU800 controller (Connection boxes and SCU800 controller was fixed to a concrete wall at low level.
  • Time taken to install complete system 48 man hours.