Cable Construction
Conductor | Solid Bare Copper Wire (18/1AWG) |
Insulation | Solid PE (Polyethylene) |
Bedding | PET (Polyester Tape) |
Filler | Halogen Free Compound |
Shield | AL/PET (Aluminium / Polyester Tape) |
Sheath | FRNC LSZH (Low Smoke Zero Halogen) Compound |
Braid | TCWB (Tinned Copper Wire Braid) 60% Coverage |
Dimensions
No. of Pairs | Nominal Cross Sectional Area mm² | Nominal Conductor Diameter mm | Nominal Insulation Diameter mm | Nominal Outer Diameter of Filler Sheath mm | Nominal Diameter of Outer Sheath mm | Nominal Weight kg/km |
---|---|---|---|---|---|---|
1 | 0.85 | 1.04 | 2.5 | 5.5 | 7.6 | 89 |
Maximum DC Conductor Resistance Ω/km | Capacitance at 800Hz pF/km | Impedance (3÷20MHz) Ω (±10%) | Impedance Ω | Attenuation dB/km | ||||
---|---|---|---|---|---|---|---|---|
31.25kHz | 39kHz | 1MHz | Maximum at 39kHz | Nominal at 100kHz | Nominal at 1MHz | |||
22 | 60 | 150 | 100 | 100 | 80 | 3 | 4 | 15 |
Inductance at 31.25 KH mH/km | Dielectric Strength kVac / 1 min | Minimum Insulation Resistance GΩ x KM | Transfer Impedance mΩ/M | Maximum Installation Pulling N | ||
---|---|---|---|---|---|---|
Conductor/Conductor | Conductor/Shield | 100kHz | 1MHz | |||
0.7 | 2.5 | 2.5 | 5 | 15 | 10 | 120 |