Cable Construction

ConductorClass 5 flexible copper conductor
InsulationLSZH (Low Smoke Zero Halogen) Type TI6
BeddingLSZH (Low Smoke Zero Halogen) Type TM7
BraidingGSWB (Galvanized Steel Wire Braid) minimum coverage of braiding shall be 50%
SheathLSZH (Low Smoke Zero Halogen) Type TM7

Dimensions

No. of CoresNominal Cross Sectional Area mm²Nominal Thickness of Insulation mmNominal Thickness of Bedding mmNominal Diameter of GSWB mmNominal Thickness of Sheath mmNominal Overall Diameter mmNominal Weight kg/km
21.50.50.50.240.88109
310.50.50.2418114
31.50.50.50.2419138
32.50.60.50.24110188
340.60.60.24112256
360.70.60.241.114352
41.50.50.50.24110161
42.50.60.50.24111223
440.60.60.24113310
460.70.60.241.115430
51.50.50.50.24110189
52.50.60.60.24112264
560.70.60.241.216523
5100.80.80.31.220822
5160.90.80.31.4241217

Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables
The below table is in accordance with BS EN 60228 (previously BS 6360)
Nominal Cross
Sectional Area mm²
Maximum Diameter of Wires in Conductor mmMaximum Resistance
of Conductor At 20ºC
Plain Wires ohms/km
10.2119.5
1.50.2613.3
2.50.267.98
40.314.95
60.313.3
100.411.91
160.411.21

Current Carrying Capacity at 30°C
Nominal Cross
Sectional Area mm²
Current Carrying Capacity
In Conduit
Amps
In Air
Amps
11220
1.51524
2.52032
42542
63354
104573
166198

Voltage Drop
Nominal Cross
Sectional Area mm²
Two Core Cable DC mV/A/mSingle-Phase
Two Core Cable
AC
mV/A/m
Three-Phase
Three Or Four Core Cable AC
mV/A/m
1444438
1.5292925
2.5181815
411119.5
67.37.36.4
104.44.43.8
162.82.82.4

De-Rating Factors
No. of Cores
57101419244448
DE-RATING FACTOR0.720.630.560.510.450.420.340.33