H07RN-F BS EN 50525-2-21 Flexible Rubber Cable

H07RN-F BS EN 50525-2-21 Flexible Rubber Cable

Cable Construction
ConductorClass 5 flexible copper conductor according to BS EN 60228 (previously BS 6360)
InsulationEPR (Ethylene Propylene Rubber) Type EI4 according to BS EN 50363
SheathPCP (Polychloroprene) Type EM2 according to BS EN 50363

Dimensions

No. of CoresNominal Cross Sectional Area mm²Nominal Thickness of Insulation mmNominal Overall Diameter mmNominal Weight kg/kmA2 Glands
Brass
A2PL Gland
Plastic
11.50.85.85220/1620S
12.50.96.56720/1620S
1417.49220/1620S
1618.111920S20S
1101.29.818520S20S
1161.211.352582020
1251.413.33752520
1351.414.64852525
1501.617.26692525
1701.619.358923232
1951.822.211603232
11201.824.314363232
1150225.917484040
11852.229.721424040
12402.431.5269850S50S
13002.636.533485050S
14002.840.442935050
1500342.652625050
1630347.2679063S63S
210.88.19420S20S
21.50.8912020S20S
22.50.910.717320S20S
24112.32392020
26113.83132525
2101.218.65633225
2161.221.78303232
2251.425.812114040
310.88.7411720S20S
31.50.89.6814720S20S
32.50.911.481232020
34113.22972525
36114.783902525
3101.219.97053232
3161.223.3110313232
3251.427.715124040
3351.430.2190750S50S
3501.635.826515050S
3701.640.134845050
3951.846.4459463S63S
410.89.6314220S20S
41.50.810.6318020S20S
42.50.912.62602020
44114.63362525
46116.44492532
4101.221.88833232
4161.225.411384040
4251.430.7171450S50
4351.433.4220450S50
4501.639.6302950-
4701.644.9412163-
4951.851.9536163-
51.50.811.82062020L
52.50.9142972525
54116.24222525
56118.25673232
5101.22410104040
5161.228.214004040
5251.433.9209650S50
5351.437.227005050
5501.644373063S63S
71.50.815.133152525
72.50.917.64452532
121.50.818.24932532
122.50.921.47023232
191.50.822.17103232

Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables
Nominal Cross
Sectional Area mm²
Maximum Diameter of Wires in Conductor mmMaximum Resistance
of Conductor At 20ºC
Plain Wires ohms/km
10.2119.5
1.50.2613.3
2.50.267.98
40.314.95
60.313.3
100.411.91
160.411.21
250.410.78
350.410.554
500.410.386
700.510.272
950.510.206
1200.510.161
1500.510.129
1850.510.106
2400.510.0801
3000.510.0641
4000.510.0486
5000.610.0384
6300.610.0287

Current Carrying Capacity and Mass Supportable (1mm² to 2.5mm²)
Nominal Cross Sectional Area mm²Current Carrying CapacityMaximum Mass Supportable By Twin Flexible Cable
(See Regulations 522.7.2 and 559.6.1.5 of the 17th Edition of IEE Wiring Regulations)
kg
Single-Phase AC
Amps
Three-Phase AC
Amps
110105
1.516165
2.525205

Voltage Drop (1mm² to 2.5mm²)
Nominal Cross
Sectional Area mm²
DC or Single-Phase AC
mV/A/m
Three-Phase AC
mV/A/m
14640
1.53227
2.51916

Conductor Operating Temperature: 60°C

Current Carrying Capacity (4mm² and above)

Nominal Cross
Sectional Area mm²
60°C Conductor Operating Temperature85°C Conductor Operating Temperature **
Single-Phase AC or DCThree-Phase ACSingle-Phase AC or DCThree-Phase AC
1 Two Core Cable, With or Without Protective Conductor
Amps
2 Single Core Cables
Amps
1 Three Core, Four Core or Five Core Cable
Amps
1 Two Core Cable, With or Without Protective Conductor
Amps
2 Single Core Cables
Amps
1 Three Core, Four Core or Five Core Cable
Amps
430-2641-36
639-3453-47
1051-4773-64
1673-6399-86
2597-83131-114
35 -140102-192140
50-175124-240170
70-216158-297216
95-258192-354262
120-302222-414303
150 -347255-476348
185-394291-540397
240-471343-645467
300-541394-741537
400-644--885-
500-738--1017-
630-861--1190-

Ambient Temperature: 30°C
Conductor Operating Temperature: 60°C/85°C
The above table is for 60°C conductor operating temperature is in accordance with T4F1A of the 17th Edition of IEE Wiring Regulations.
** 85°C Table is in accordance with Table 4H2A of the 16th Edition of IEE Wiring Regulations.

 

The current ratings arranged are for cables in free air but may also be used for cables resting on the surface. If the cable is to be wound on a drum on load the ratings should be reduced in accordance with Note 2 below and for cables which may be covered, see Note 3.

Note 2: Flexible cables wound on reeling drums
The current ratings of cables used on reeling drums are to be reduced by the factors below:

A. Radial Type Drum
-Ventilated: 85%
-Unventilated: 75%

B. Ventilated Cylindrical Type Drum
-1 Layer of cable: 85%
-2 Layer of cable: 65%
-3 Layer of cable: 45%
-4 Layer of cable: 35%

A Radial Type Drum is where spiral layers of cable are accommodated between closely spaced fittings. If fitted with solid flanges the ratings given should be reduced and the drum is described as non-ventilated. If the flanges have suitable apertures the drum is described as ventilated.

A ventilated cylindrical cable drum is where layers of cable are accommodated between widely spaced flanges and the drum and end flanges have suitable ventilating apertures.

3. Where cable may be covered or coiled up whilst on load, or in air movement over the cable restricted, the current rating should be reduced.

It is not possible to specify the amount of reduction but the table of rating factors for reeling drums can be used as a a guide.

Voltage Drop (4mm² and above)

Nominal Cross
Sectional Area mm²
Two Core Cable, DC
mV/A/m
Two Core Cable,
Single-Phase AC
mV/A/m
1 Three Core, Four Core or Five Core Cable,
Three-Phase AC
mV/A/m
2 Single Core Cables,
Touching
DC
mV/A/m
Single-Phase AC
mV/A/m
4121210--
67.87.86.7--
104.64.64--
162.92.92.5--
251.81.80.1751.851.550.151.55----
35- ---1.10.151.151.311.310.211.32
50- ---0.830.1450.840.910.910.210.93
70----0.570.140.580.640.640.20.67
95----0.420.1350.440.490.490.1950.53
120----0.330.1350.360.380.380.190.43
150----0.270.130.30.310.310.190.36
185----0.220.130.260.250.250.190.32
240----0.170.130.210.190.1950.1850.27
300----0.1350.1250.1850.150.1550.180.24
400-------0.1150.120.1750.21
500-------0.090.0990.170.2
630-------0.0680.0790.170.185

Conductor Operating Temperature: 60°C
r = Resistive Component
x = Reactive Component
z = Impedance Value
* A larger voltage drop will result if the cables are spaced

 

De-Rating Factors

Ambient Temperature °C
3540455055
DE-RATING FACTOR0.910.820.710.580.41

power-accessories01

Our power cables have many accessories.

For more information, don’t hesitate to call us on 0121 508 6890 or get in touch via our Contact Page.

H07RN-F BS EN 50525-2-21 Flexible Rubber Cable

Coil End Lead Type 4 BS 6195 Cable

Cable construction

ConductorClass 5 flexible tinned copper conductor according to BS EN 60228 (previously BS 6360)
Insulation4A, 4C: EPR-HOFR (Ethylene Propylene Rubber - Heat and Oil Resistant and Flame Retardant) Type FR1 according to BS 7655
4D, 4E, 4F: EPR-HOFR (Ethylene Propylene Rubber - Heat and Oil Resistant and Flame Retardant) Type FR2 according to BS 7655
BeddingPET (Polyester Type)
SheathCPE (Chlorinated Polyethylene) rubber compound

Dimensions - Coil End Lead TYPE 4 BS 6195 Cable

No. of CoresNominal Cross Sectional Area mm²Nominal Thickness of Insulation mmNominal Overall Diameter mmNominal Weight kg/km
Coil End Lead Type 4A Cable - 300/500V
11.50.8429
12.50.94.642
1415.461
1616.588
1101.27.9141
Coil End Lead Type 4C Cable - 600/1000V
1101.58.5130
1161.59.6190
1251.68.5290
1351.612.8380
1501.714.8510
1701.817.2750
195219.7935
11202.221.91160
11502.324.11450
11852.426.31770
12402.428.32260
13002.6332760
14002.837.43880
15003.2384650
16303.3436220
Coil End Type 4D Cable - 1.9/3.3kV
12.52.88.5100
142.89.1115
162.810.3141
1102.811.3216
1162.812.4288
1252.813.8392
1352.815.2509
1502.817.1682
1702.819.2894
1953221168
1120323.51433
1150325.51734
1185327.52073
1240330.62657
1300333.83279
1400337.84229
Coil End Type Lead 4E Cable - 3.8/6.6kV
116517.2408
125518.6527
135520656
150522.1832
170524.21053
195526.31304
1120527.81634
1150529.81894
1185532.12242
1240535.12842
Coil End Type 4F Cable - 6.35/11kV
1257.624.1764
1357.625.5911
1507.627.31114
1707.629.41344
1957.631.51610
11207.633.31919
11507.635.32248
11857.637.32616
12407.640.33252

Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables
Nominal Cross
Sectional Area mm²
Maximum Diameter of Wires in Conductor mmMaximum Resistance
of Conductor At 20ºC
Plain Wires ohms/km
1.50.2613.3
2.50.267.98
40.314.95
60.313.3
100.411.91
160.411.21
250.410.78
350.410.554
500.410.386
700.510.272
950.510.206
1200.510.161
1500.510.129
1850.510.106
2400.510.0801
3000.510.0641
4000.510.0486
5000.610.0384
6300.610.0287

Current Carrying Capacity in Free Air
Nominal Cross
Sectional Area mm²
Maximum Continuous Current Rating
Single Cable
Amps
2 Cables Bunched
Amps
3 Cables Bunched
Amps
1.5-2522
2.5-3430
4-4641
6-5853
10-8073
16-10897
25166147128
35206182160
50250220197
70321282254
95391343311
120455398364
150525459422
185602523485
240711618577
300821713670
400989855790
5001140986908
630132311411047

De-Rating Factors
Ambient Temperature °C
253035404550556065
DE-RATING FACTOR1.141.091.051.000.950.900.840.770.71

Ambient temperature: 40ºC
Conductor operating temperature: 90ºC

Notes
The current-carrying capacities in this appendix are based upon the following reference ambient temperatures:
1. For non-sheathed and sheathed cables in air, regardless of the installation method: 30ºC
2. For buried cables, either directly in the soil or in ducts in the ground: 20ºC

The current rating shown are based on conservative assumptions, and therefore, in some instances, may be adjusted according to the ambient installation and operating conditions.

power-accessories01

Our power cables have many accessories.

For more information, don’t hesitate to call us on 0121 508 6890 or get in touch via our Contact Page.

318-TRS / H05RR-F BS EN 50525-2-21 Cable

318-TRS / H05RR-F BS EN 50525-2-21 Cable

Cable Construction
ConductorClass 5 flexible copper conductor according to BS EN 60228 (previously BS 6360)
InsulationRubber Compound Type E14 according to BS EN 50363
SheathRubber Compound Type EM3 according to BS EN 50363

Dimensions

No. of CoresNominal Cross Sectional Area mm²Nominal Thickness of Insulation mmNominal Overall Diameter mmNominal Weight kg/km
20.750.66.153
210.66.664
21.50.87.895
22.50.99.2140
24110.8180
30.750.66.665
310.6777
31.50.88.4115
32.50.99.9170
34111.7240
36113.3320
40.750.67.380
410.67.695
41.50.89.4145
42.50.911.1210
44113300
46114.5405
50.750.68.1100
510.68.4115
51.50.810.3170
52.50.912.4255
54114.5355

Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables
Nominal Cross
Sectional Area mm²
Maximum Diameter of Wires in Conductor mmMaximum Resistance
of Conductor At 20ºC
Plain Wires ohms/km
0.750.2126
10.2119.5
1.50.2613.3
2.50.267.98
40.314.95
60.313.3

Current Carrying Capacity and Mass Supportable
Nominal Cross Sectional Area mm²Current Carrying CapacityMaximum Mass Supportable By Twin Flexible Cable
(See Regulations 522.7.2 and 559.6.1.5 of the 17th Edition of IEE Wiring Regulations)
kg
Single-Phase AC
Amps
Three-Phase AC
Amps
0.75663
110105
1.516165
2.525205
432255
The table above is in accordance with Table 4F3A of the 17th Edition of IEE Wiring Regulations.

Voltage Drop

Nominal Cross
Sectional Area mm²
DC or Single-Phase AC
mV/A/m
Three-Phase AC
mV/A/m
0.756254
14640
1.53227
2.51916
41210
The table above is in accordance with Table 4F3B of the 17th Edition of IEE Wiring Regulations.

De-Rating Factor for Ambient Temperature 60°C Thermoplastic or Thermosetting Insulated Cords

Air Temperature °C
3540455055
DE-RATING FACTOR0.910.820.710.580.41
The table above is in accordance with Table 4F3A of the 17th Edition of IEE Wiring Regulations

 

power-accessories01

Our power cables have many accessories.

For more information, don’t hesitate to call us on 0121 508 6890 or get in touch via our Contact Page.

318-TRS / H05RR-F BS EN 50525-2-21 Cable

0361TQ BS EN 60332-1-2 BS 638 Black Welding Cable

Cable Construction

Conductor16mm² to 95mm²: Class 6 extra flexible copper conductor according to BS EN 60228 (previously BS 6360)
120mm² and above: Class 5 flexible copper conductor
InsulationEPR (Ethylene Propylene Rubber) Type GP4 according to BS 7655
BeddingPET (Polyester Type)
SheathHOFR (Heat and Oil Resistant and Flame Retardant) Type EM5 according to BS EN 50363

Dimensions - Type 0361TQ - Plain Copper Conductors

Conductor ClassNominal Cross Sectional Area mm²Total Radial Thickness of Covering mmNominal Overall Diameter mmNominal Weight kg/km
61629.7215
625211.2305
635212.4400
6502.214.3587
6702.416.3775
6952.618.61040
51202.820.31256
5150322.61360
51853.224.71875
52403.427.82534

Class 6 Flexible Copper Conductors for Single Core and Multi-Core Cables
Nominal Cross
Sectional Area mm²
Maximum Diameter of Wires in Conductor mmMaximum Resistance
of Conductor At 20ºC
Plain Wires ohms/km
160.211.21
250.210.78
350.210.554
500.210.386
700.210.272
9950.210.206

Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables
Nominal Cross
Sectional Area mm²
Maximum Diameter of Wires in Conductor mmMaximum Resistance
of Conductor At 20ºC
Plain Wires ohms/km
1200.510.161
1500.510.129
1850.510.106
2400.510.0817

Duty Cycle and Current carrying Capacity
The current carrying capacity of a welding depends on the length of the duty cycle. The duty cycle is the length of time in which a loaded current passes through the cable over an operation period time of 5 minutes, indicated as a percentage of that period. For example, if the current is flowing for the whole 5 minutes, the duty cycle is 100% and if the current is only flowing for 1 minute, the duty cycle is 20%.
As conductor temperature differs according to the in use as well as current, ratings displayed are given as a guide.
The permissible loading of the cable for duty cycles other than those displayed in the table can be calculated using the following formula:
I =  I100 x √100/F

Where:
I = the maximum permissible loading current for the required duty cycle
I100 =  the maximum permissible loading current for a duty cycle of 100%
F = the required duty cycle calculated as a percentage of the 5 minute operation period

Typical guidance values for different welding processes are as follows:
Fully Automatic Welding 100%
Semi-Automatic Welding 65-85%
Manual Welding 30-60%
Very Infrequent or Occasional Welding 20%

Current Carrying Capacity
The below table is in accordance with Table A.5 of BS 638 Part 4

Nominal Cross Sectional Area mm²Current Rating for Single Cycle Operation Over a Maximum Period of 5 Minutes
Amps
100%85%60%35%
16135145175230
25180195230300
35225245290375
50285305365480
70355385460600
95430470560730
120500540650850
150580630750980
1856657208601120
2407808509751250

De-Rating Factors
The below table is in accordance with Table A.7 of BS 638 Part 4
Ambient Temperature °C
2530354045
DE-RATING FACTOR1.00.960.910.870.82